SKU : N/A Category :

Magnetic Float Lel SENSOR

23.00 $36.00 $

Specifications:

  • Sensor resolution: Standard type: 5 % (21 levels) or 10 % (11 levels)
    Full Steps type: 1 % (continuous levels every 2 cm)
  • Sensor accuracy: Standard type: ± 1 cm for any level reading
    Full Steps type: ± 1 mm for any level reading
  • Length range: 20 cm to 6 meters
  • Sensor output: Standard type: 1 Kohm – 23 Kohm discontinuous output
    Full Steps type: 10 ohm -190 ohm continuous output (or customized)
  • Sensor material: PVC and Aluminum (special order for Stainless Steel 316L)
  • Floater material: Buna N float with built in permanent magnets
  • Floater dimension: 32 mm diameter x 36 mm length
  • Flange dimension: 70 mm diameter, 5 holes for installation with adjustable positioning
  • Working temperature: -20˚C up to around +80˚C
  • Tank hole size: Between 33 ~ 37 mm diameter
  • Degree of protection: IP68 for the electronic circuit from fluids and dust
    Sensitive for harsh shocks and strong vibrations
    Allowable longitudinal bending is no more than 1 cm per 1 meter

Additional information

sensor size 10%

1m, 1.25m, 1.5m, 1.75m, 2m

Description
– Axial type with vertical motion of a magnetic floater
– Widely used in tanks as diesel, water, sewage, oil
– Level range from 20 cm up to 6 meters
– Digital monitoring with 2 wires signal
– Easy installation with a moving flange
– High quality magnetic reed switch
– Excellent operating lifespan service
– Anti-corrosion heavy duty structure
– Safe to use in flammable liquids
– Complete isolation between liquid
and electronic circuit (IP68)
User interface
To install the level sensor:
 Make a hole on the top of the tank with a
diameter between 33 and 37 mm
 Insert the probe into the tank until it reaches the bottom
 Adjust the flange position and fix it on the top of the tank
o The level sensor standard sizes: 1 meter, 1.25 meter, 1.5 meter,
1.75 meter, 2 meters and any else will be made on demand
o N.B. In case the sensor wires are set up in area where there is
high power cables or with high frequency lines (parasite field),
it is preferred to use a shielded cable or a coaxial cable for
the sensor extension to prevent reading disturbance